Diplomski rad sadrži proračun i analizu sustava grijanja i hlađenja turističko-ugostiteljskog objekta površine 275 m2 i dodatnog objekta površine 100 m2 na mjestu Rastoka, vodeničarskog prigradskog naselja, grada Slunja. Kao sustav grijanja i hlađenja objekata odabrana je dizalica topline voda-voda koja za izvor/ponor topline koristi rijeku Slunjčicu srednje godišnje temperature 11,5°C, a ogrjevno rashladna tijela ĉine ventilokonvektori i ljestve. Prvi dio sadrži proračun toplinskog i rashladnog opterećenja ugostiteljskog objekta izraženog pomoću programa IntegraCad koji se koristi u termotehniĉkim projektantskim uredima. Proračun obuhvaća toplinske gubitke zimi prema pojednostavljenoj normi E\N 12 831 te proračuna toplinskih dobitaka ljeti prema normi VDI 2078. U drugom dijelu na temelju prethodnog proračuna toplinskog i rashladnog opterećenja proračunate su komponente dizalice topline. Dobiveni učini kondenzatora, isparivača te snaga kompresora odredili su veličine izmjenjivača te odabir realnog kompresora, a samim time i razvodnog sustava te pad tlaka. U radu je prikazana i tehnička, ekonomska te ekološka usporedba dizalice topline s konvencionalnim sustavom grijanja sa svojom shemom spajanja i automatske regulacije.

Abstract

Thesis includes calculation and analysis of heating and cooling systems of tourist facility estimated area of 275 m2 and an additional building area of 100 m2 at Rastoke watermill suburban, city of Slunj. As heating and cooling system, water-to-water heat pump was selected with river Slunjĉica as a coolant of mean annual temperature 11,5°C. Fancoils and ladders are used as heating and cooling units. The first part contains the heating and cooling load calculations of tourist facility elaborated by IntegraCad used in HVAC planning offices. The calculation includes heat losses in winter by standard EN 12831 and heat gain in the summer according to VDI 2078 norm. Based on previous calculations, components of heat pumps are calculated. So obtained condenser, evaporator and compressor powers determined size of heat exchangers, pipelines and corresponding equipment. The thesis also contains a technical, economic and environmental impact comparison of heat pumps with conventional heating systems with its wiring diagram and automatic control system.

Item Type: Thesis (Master's thesis (Bologna))
Uncontrolled Keywords: dizalica topline voda-voda; proračun komponenti sustava; proračun toplinskog opterećenja; ekonomska analiza
Keywords (Croatian): water-to-water heat pump; heating-cooling load calculation; calculation of system components; economic analysis