Eksperimentalno-numerička analiza uštede energije za hlađenje zgrade kod primjene visokoreflektivnog premaza fasade

Kralj, Tomislav (2017) Eksperimentalno-numerička analiza uštede energije za hlađenje zgrade kod primjene visokoreflektivnog premaza fasade. = Experimental and numerical analysis of cooling energy need using high-reflective facade coating. Master's thesis (Bologna) , Sveučilište u Zagrebu, Fakultet strojarstva i brodogradnje, UNSPECIFIED. Mentor: Dović, Damir.

[img]
Preview
Text
Kralj_2017_diplomski.pdf - Published Version Jezik dokumenta:Croatian

Download (3MB) | Preview
[img] Text
Kralj_Tomislav_autorska_izjava_diplomski_2017.pdf - Published Version
Restricted to Repository staff only Jezik dokumenta:Croatian

Download (506kB)

Abstract (Croatian)

U ovom radu analiziran je potencijal uštede potrebne toplinske energije za hlađenje zgrade kod primjene visokoreflektivnog premaza za fasade. U eksperimentalnom dijelu, primjenom infracrvene termografije određen je emisijski faktor dugovalnog zračenja visokoreflektivnog premaza za fasade. Metalne ploče sa i bez visokoreflektivnog premaza izložene su Sunčevom zračenju te su istovremeno izmjerene njihove temperature i bitni meteorološki parametri. Rezultati mjerenja iskorišteni su u matematičkom modelu za određivanje faktora apsorpcije kratkovalnog Sunčevog zračenja svih ispitivanih površina ploča. U numeričkom dijelu proveden je proračun godišnje potrebne toplinske energije za grijanje i hlađenje, prema normi HRN EN ISO 13790, za odabrani model zgrade sa i bez visokoreflektivnog premaza. Proračun je proveden za tri različite razine specifične potrebne toplinske energije za grijanje (10 kWh/m2a, 70 kWh/m2a i 150 kWh/m2a) koje su postignute s faktorom apsorpcije fasade 0,4. Također su određene vrijednosti ukupne isporučene energije i troškova energije. Na kraju je prikazana analiza utjecaja faktora apsorpcije Sunčevog zračenja na troškove energije, isporučenu energiju i godišnju potrebnu toplinsku energiju za grijanje i hlađenje.

Abstract

In this thesis, the potential for savings in net cooling energy need by using a high-reflective facade coating is analysed. In the experimental part, longwave emissivity of the high-reflective facade coating is determined by means of infrared thermography. Metal plates with and without high-reflective coating are exposed to solar radiation and their temperatures and relevant weather parameters are simultaneously measured. Measurement results are used in a mathematical model for calculation of solar absorptance of all observed plate surfaces. In the numerical part, the calculations of annual net heating and cooling energy need are done according to the HRN EN ISO 13790 standard, for a model of a building with and without high-reflective facade coating. The calculations are done for three different values of annual heating energy need (10 kWh/m2a, 70 kWh/m2a and 150 kWh/m2a), which are achieved with solar absorptance of the facade equal to 0,4. Values of total purchased energy and costs of energy are also determined. Finally, the analysis of influence of solar absorptance of the facade on the costs of energy, total purchased energy and annual net heating and cooling energy is shown.

Item Type: Thesis (Master's thesis (Bologna))
Uncontrolled Keywords: visokoreflektivni premaz; fasada; termografija; hlađenje zgrada; faktor apsorpcije Sunčevog zračenja
Keywords (Croatian): high-reflective coating; facade; thermography; building cooling; solar absorptance
Subjects: TECHNICAL SCIENCE > Mechanical Engineering
Divisions: 300 Department of Thermodynamics, Thermal and Process Engineering > 320 Chair of Thermal and Process Engineering
Date Deposited: 30 Nov 2017 09:06
Last Modified: 11 Dec 2017 16:08
URI: http://repozitorij.fsb.hr/id/eprint/8133

Actions (login required)

View Item View Item

Downloads

Downloads per month over past year

Nema podataka za dohvacanje citata